Automatic start

Generator Not Starting Automatically

This page is for a standby generator that should start on its own when the mains fails, and does not. A set that will not start at all, even from the manual button, belongs on the generator not starting page. The difference is the automatic sequence.

  • Mains-fail sequence
  • Manual start is a useful clue
  • ATS and controller checked
  • Onsite across Gauteng
Technicians reading a generator controller beside an open automatic transfer switch

When the supply drops

Why doesn't my generator start when the power goes off?

Because the automatic path never asked it to, or asked it and the start was blocked. Possible causes include the ATS not sending a start signal, the controller left out of automatic, a battery or charger problem, an emergency stop, a shutdown alarm, a wiring input, a mains-sensing fault, or a fuel and starter fault that only shows once a start is requested.

A useful split is whether the engine will start from the panel in manual. If manual works and automatic does not, the engine is less likely to be the first fault. If manual also fails, the visit includes the battery and the starter path as well as the switch.

The full sequence is what gets tested: mains fail, start request, crank, running, and only then transfer. Proving one of those steps does not prove the next.

Wiring at a generator controller checked during an automatic-start fault

The steps that can stop it

Start signal, controller, battery and a failed attempt

  • ATS start-signal problems

    The switch may not have seen the mains fail, or it may have seen it and not passed a start to the generator.

  • Generator controller problems

    Manual mode, an uncleared shutdown, or an input the module does not accept will ignore a genuine mains failure.

  • Battery and charging problems

    A set that sits can have a flat battery or a charger that is not holding it. Automatic start needs that battery when nobody is there to jump it.

  • Generator starts manually but not automatically

    That pattern points at the request and the mode, not at a seized engine.

  • Generator attempts to start but fails

    It cranks, or it fires and drops out, after the request arrives. Fuel and shutdowns then join the test. That is different from a set that never tries.

  • Testing the complete automatic start sequence

    The visit follows mains fail through to a running generator. Transfer of the building is the ATS page if the engine is already up and the lights are still out.

Google reviews of ProService Generator Repairs

  • Google Review

    They updated the proprietary firmware on our Generac commercial diesel controller, completely resolving the intermittent starting issues we had been battling for months.

  • Google Review

    Excellent residential generator maintenance in Bryanston. They are quiet, efficient, and replaced our failing battery charger during load shedding.

Common Questions

Questions about generators that do not auto start

What does not auto starting mean?

The standby set does not start by itself when the mains supply fails.

Is this the same as a generator that will not start at all?

No. A set that also fails in manual is a general no-start. This page is the automatic sequence.

It starts when I press the button. Why does the outage not start it?

Possible causes include no start signal from the ATS, the controller not being in automatic, or an alarm that only blocks that path.

Can a flat battery stop an automatic start?

Yes. A charger fault will flatten the battery between outages, so the set is dead when the mains drops.

There is an emergency stop pressed. Does that block auto start?

Yes. An emergency stop or a latched shutdown will hold the start off until it is cleared for a real reason.

The generator cranks when the power fails but does not fire. Where does that sit?

The start request arrived. Fuel and a crank-no-fire fault are then part of the test, on the cranks-but-will-not-start page if that is the whole symptom.

Should I force the transfer switch?

No. The sequence is tested without bridging live gear or defeating a shutdown.

Still unsure what the fault is? Call or WhatsApp 082 057 4605 for onsite diagnosis.

Service Areas

Onsite visits across Gauteng

Technicians travel to the generator. These are the main Gauteng areas. Suburb pages sit under each region.

What to send before we attend

ProService Generator Repairs confirms an onsite visit from these details. Send what you have. A missing model number does not stop the booking.

Location
The suburb or site, so the visit can be booked in the right area.
Make and model
The generator brand and model, if they are known.
kVA
The size printed on the data plate.
Fuel type
Diesel, petrol, LPG, natural gas, or dual-fuel.
Controller model
The module name on the panel, when it is visible.
Fault or alarm
What the set does, and any text on the screen.
Photos
The generator, the data plate, and the controller or alarm. Send these on WhatsApp.

Book a Visit

Say what happens when the mains fails

Tell us if it does nothing, clicks, cranks, or starts only when you use manual.