Skip to main content

kVA and kW

Generator kVA to kW Explained

kVA is apparent power. kW is real, usable power. They are related by power factor: kW = kVA × power factor. Generators are often rated in kVA because the alternator has to supply current, not only the kilowatts the load consumes. Do not assume every set uses the same power factor. Read the plate.

  • kVA is not kW
  • 0.8 is only an example
  • The plate beats the conversion
  • Onsite across Gauteng
Technician tracing labelled wires in a generator control panel

Apparent power and real power

Why are generators rated in kVA?

The alternator is limited by current and voltage, which is what kVA describes. The kilowatts you can use depend on the power factor of the load. A heater is different from a motor. That is why a conversion done with the wrong power factor sizes the set incorrectly.

A common example on standby sets is a power factor of 0.8. At that example only, 100 kVA × 0.8 = 80 kW. If the plate shows a different power factor, use the plate. The table further down is labelled as an example at 0.8. It is not a claim that your generator is 0.8.

Three-phase sets add balance across the phases. Motor starting current can be several times the running kilowatts. Sizing from a kW total on a spreadsheet, without the power factor, the phase and the starting load, is how a set looks large enough and still trips.

Commercial generator installation where the plate kVA, not a kW guess, sizes the set

Using the numbers

Power factor, motors and phase

  • Why power factor matters

    Power factor is the share of apparent power that becomes real power. Change the factor and the kW result changes. One conversion does not fit every site.

  • Three-phase considerations

    A three-phase rating is for a three-phase system. Unbalanced single-phase loads on that set do not get to use the full kVA. Phase is a separate guide.

  • Motor starting loads

    The running kW of a motor is not the current it draws as it starts. A set can be inside its kW rating and still bog down or trip on starting.

  • Why sizing is not only kW

    Voltage, frequency, phase, power factor and starting current all sit beside kilowatts. The sizes page is where those are applied to a booking.

Example at 0.8 power factor

Arithmetic only, using kW = kVA × 0.8. Use these figures solely when the data plate power factor is 0.8. Otherwise use the kW printed on the plate.

  • 5 kVA

    4 kW

  • 10 kVA

    8 kW

  • 20 kVA

    16 kW

  • 30 kVA

    24 kW

  • 50 kVA

    40 kW

  • 100 kVA

    80 kW

  • 150 kVA

    120 kW

  • 200 kVA

    160 kW

  • 250 kVA

    200 kW

  • 500 kVA

    400 kW

  • 750 kVA

    600 kW

  • 1000 kVA

    800 kW

Google reviews of ProService Generator Repairs

  • Google Review

    Cummins engines require absolute precision, and their mechanics delivered exactly that during our 500kVA service, using genuine filters and providing a comprehensive diagnostic engine report.

  • Google Review

    Baudouin engines are heavy-duty beasts, and this team services our 1000kVA unit perfectly, resolving a persistent cooling issue that other contractors couldn't figure out.

Common Questions

Questions about kVA and kW

What is the difference between kVA and kW?

kVA is apparent power. kW is real power. kW = kVA × power factor.

Is 100 kVA the same as 100 kW?

No. At a power factor of 0.8, 100 kVA is 80 kW. That 0.8 is an example. Your plate may differ.

Why do generator plates show kVA?

Because the alternator’s limit is voltage and current. Usable kilowatts depend on the load’s power factor.

Can I size a generator from kW alone?

No. Power factor, phase and motor starting current change what the set must supply.

Does every generator have a 0.8 power factor?

No. 0.8 is a common example. Read the power factor on the data plate before converting.

How do three-phase loads affect the rating?

The rating assumes the load is shared across the phases. A heavy load on one phase can overload that phase inside the nameplate kVA.

Where do I see the real numbers for my set?

On the generator data plate: kVA, kW if printed, voltage, and power factor. The data-plate guide walks through those fields.

Will a conversion tell me if the set can run the building?

It converts units. It does not test the building. A load test is the check when capacity is the question.

Still unsure what the fault is? Call or WhatsApp 082 057 4605 for onsite diagnosis.

Service Areas

Onsite visits across Gauteng

Technicians travel to the generator. These are the main Gauteng areas. Suburb pages sit under each region.

What to send before we attend

ProService Generator Repairs confirms an onsite visit from these details. Send what you have. A missing model number does not stop the booking.

Location
The suburb or site, so the visit can be booked in the right area.
Make and model
The generator brand and model, if they are known.
kVA
The size printed on the data plate.
Fuel type
Diesel, petrol, LPG, natural gas, or dual-fuel.
Controller model
The module name on the panel, when it is visible.
Fault or alarm
What the set does, and any text on the screen.
Photos
The generator, the data plate, and the controller or alarm. Send these on WhatsApp.

Book a Visit

Send a photo of the rating plate

kVA, kW and power factor on the plate are more useful than a conversion done from memory.

Include what you have. Photos of the generator and the data plate can be sent on WhatsApp.

Chat with us on WhatsApp